HOME INTRANET KOREAN ENGLISH JAPANESE MONGOLIA
> Products > POWERケーブル > TFR-CV


  ESS CABLE (Special Rubber Insulated Cable)
Application Cable with good electrical, physical and chemical properties for use in circuits for power or control of 600V
Construction Conductor: Electrical Interlocking
Insuation : XLPE
Sheathed : PVC
Insulation Color 2core:BK,WH 3core:BK,WH,RD
4core:BK, WH, RD, GN
More than 5core : numbering


Single Core
Conductor Thickness of
insulation
Specified value
Sheathed
Thickness
Approx
Overall
Diameter
Max. Conductor
Resistance 20℃
Test
Voltage
Approx.
Weight
Standard
Lenght
Nominal cross
-sectional
area
Number&
Diameter
Outer
Diameter
mm2 No./mm mm mm mm mm Ω/km V/5min Kg/km m
1.5 7/0.53 1.59 0.7 1.4 6.3 3500 12.1 53 300
2.5 7/0.67 2.01 0.7 1.4 6.7 7.41 65 300
4 7/0.85 2.55 0.7 1.4 7.2 4.64 81 300
6 7/1.04 3.12 0.7 1.4 7.8 3.08 108 300
10 7/1.35 4.05 0.7 1.4 9.4 1.83 155 300
16 compact-round 4.7 0.7 1.4 10 1.15 210 300
25 5.9 0.9 1.4 12 1.727 315 300
35 6.9 0.9 1.4 13 1.524 414 300
50 8.1 1 1.4 14.5 0.387 542 300
70 9.8 1.1 1.4 16 0.268 761 300
95 11.4 1.1 1.5 18.5 0.193 1026 300
120 12.9 1.2 1.5 20 0.153 1279 300
150 14.4 1.4 1.6 22 0.124 1524 300
185 15.9 1.6 1.6 24 0.0991 1872 200
240 18.3 1.7 1.7 27 0.0754 2391 200
300 20.5 1.8 1.8 30 0.0601 3023 200
400 23.2 2 1.9 34 0.047 3975 150
500 26.4 2.2 2 37 0.0366 4894 150
630 33 2.4 2.2 42 0.0283 6283 150
Two Cores
Conductor Thickness of
insulation
Specified value
Sheathed
Thickness
Approx
Overall
Diameter
Max. Conductor
Resistance 20℃
Test
Voltage
Approx.
Weight
Standard
Lenght
Nominal cross
-sectional
area
Number&
Diameter
Outer
Diameter
mm2 No./mm mm mm mm mm Ω/km V/5min Kg/km m
1.5 7/0.53 1.59 0.7 1.8 11 3500 12.1 127 300
2.5 7/0.67 2.01 0.7 1.8 12 7.41 153 300
4 7/0.85 2.55 0.7 1.8 13 4.64 197 300
6 7/1.04 3.12 0.7 1.8 14 3.08 252 300
10 7/1.35 4.05 0.7 1.8 17 1.83 357 300
16 compact-round 4.7 0.7 1.8 18.5 1.15 487 300
25 5.9 0.9 1.8 22 1.727 720 300
35 6.9 0.9 1.8 24 1.524 943 300
50 8.1 1 1.8 27 0.387 1229 300
70 9.8 1.1 1.8 31 0.268 1702 300
95 11.4 1.1 1.9 35 0.193 2285 300
120 12.9 1.2 2 38 0.153 2890 300
150 14.4 1.4 2.2 43 0.124 3475 300
185 15.9 1.6 47 0.0991 4282 200
240 18.3 1.7 2.5 53 0.0754 5469 200
300 20.5 1.8 2.6 58 0.0601 6876 200
Three Core
Conductor Thickness of
insulation
Specified value
Sheathed
Thickness
Approx
Overall
Diameter
Max. Conductor
Resistance 20℃
Test
Voltage
Approx.
Weight
Standard
Lenght
Nominal cross
-sectional
area
Number&
Diameter
Outer
Diameter
mm2 No./mm mm mm mm mm Ω/km V/5min Kg/km m
1.5 7/0.53 1.59 0.7 1.8 11.5 3500 12.1 148 300
2.5 7/0.67 2.01 0.7 1.8 12.5 7.41 189 300
4 7/0.85 2.55 0.7 1.8 13.5 4.64 245 300
6 7/1.04 3.12 0.7 1.8 14.5 3.08 321 300
10 7/1.35 4.05 0.7 1.8 18 1.83 464 300
16 compact-round 4.7 0.7 1.8 19.5 1.15 649 300
25 5.9 0.9 1.8 23 1.727 975 300
35 6.9 0.9 1.8 25 1.524 1287 300
50 8.1 1 1.8 29 0.387 1693 300
70 9.8 1.1 1.9 33 0.268 2383 300
95 11.4 1.1 2 37 0.193 3224 300
120 12.9 1.2 2.1 41 0.153 4036 300
150 14.4 1.4 2.3 46 0.124 4840 300
185 15.9 1.6 2.4 50 0.0991 5975 200
240 18.3 1.7 2.6 57 0.0754 7641 200
300 20.5 1.8 2.7 62 0.0601 9638 200
Four Cores
Conductor Thickness of
insulation
Specified value
Sheathed
Thickness
Approx
Overall
Diameter
Max. Conductor
Resistance 20℃
Test
Voltage
Approx.
Weight
Standard
Lenght
Nominal cross
-sectional
area
Number&
Diameter
Outer
Diameter
mm2 No./mm mm mm mm mm Ω/km V/5min Kg/km m
1.5 7/0.53 1.59 0.7 1.8 12.5 3500 12.1 179 300
2.5 7/0.67 2.01 0.7 1.8 13.5 7.41 226 300
4 7/0.85 2.55 0.7 1.8 14.5 4.64 305 300
6 7/1.04 3.12 0.7 1.8 16 3.08 397 300
10 7/1.35 4.05 0.7 1.8 20 1.83 585 300
16 compact-round 4.7 0.7 1.8 22 1.15 816 300
25 5.9 0.9 1.8 26 1.727 1242 300
35 6.9 0.9 1.8 28 1.524 1661 300
50 8.1 1 1.9 32 0.387 2215 300
70 9.8 1.1 2 36 0.268 3110 300
95 11.4 1.1 2.1 42 0.193 1207 300
120 12.9 1.2 2.3 46 0.153 4307 300
150 14.4 1.4 2.4 51 0.124 6327 300
185 15.9 1.6 2.6 56 0.0991 7846 200
240 18.3 1.7 2.8 63 0.0754 10038 200
300 20.5 1.8 3 70 0.0601 12609 200