> Бүтээгдэхүүн > Хяналтын кабель >
0.6/1kV PVC Insulated PVC Sheathed Flexible Power Cable |
0.6/1kV PVC Insulated PVC Sheathed Flexible Power Cable (VCT) |
|
|
|
Application |
This cord is commonly used for connecting mobile electric apparatus under AC 0.6/1KV as a power source lead wire in factory, mine, or farm. |
Construction |
Conductor : Flexible Stranded Annealed Copper (Class 5)
Insulation : PVC/A COMPOUND
Sheath : PVC/ST1 COMPOUND |
Color |
- 2Core Black, White
- 3Core Black, White, Green
- 4Core Black, White, Green, Red |
Temperature Rating |
70 ℃ |
Standard |
KS C IEC 60502-1 |
Marking |
㉿ KS C IEC 60502-1 0.6/1kV VCT 00mm²×0C KISEONG 0000 RoHS |
|
|
|
Conductor |
Thickness of
insulation
Specified value |
Sheathed
Thickness |
Mean
Overall
Diameter |
Max. Conductor
Resistance 20℃ |
Test
Voltage |
Approx.
Weight |
Packing
Length |
Nominal cross
-sectional
area |
Maximum
Diameter
of wire |
Approx.
Diameter |
Copper |
Tinned |
mm² |
mm |
mm |
mm |
mm |
mm |
Ω/km |
Ω/km |
kV |
kg/km |
m |
1.0 |
0.21 |
1.3 |
0.8 |
1.4 |
6.0 |
19.5 |
20.0 |
3.5 |
50 |
300 |
1.5 |
0.26 |
1.4 |
0.8 |
1.4 |
6.5 |
13.3 |
13.7 |
3.5 |
60 |
300 |
2.5 |
0.26 |
1.8 |
0.8 |
1.4 |
7.0 |
7.98 |
8.21 |
3.5 |
80 |
300 |
4 |
0.31 |
2.3 |
1.0 |
1.4 |
8.0 |
4.95 |
5.09 |
3.5 |
100 |
300 |
6 |
0.31 |
2.8 |
1.0 |
1.4 |
9.0 |
3.30 |
3.39 |
3.5 |
130 |
300 |
10 |
0.41 |
3.6 |
1.0 |
1.4 |
10.0 |
1.91 |
1.95 |
3.5 |
180 |
300 |
16 |
0.41 |
4.5 |
1.0 |
1.4 |
11.0 |
1.21 |
1.24 |
3.5 |
240 |
300 |
25 |
0.41 |
5.6 |
1.2 |
1.4 |
13.0 |
0.780 |
0.795 |
3.5 |
350 |
100 |
35 |
0.41 |
6.7 |
1.2 |
1.4 |
14.5 |
0.554 |
0.565 |
3.5 |
450 |
100 |
50 |
0.41 |
8.0 |
1.4 |
1.4 |
16.5 |
0.386 |
0.393 |
3.5 |
610 |
100 |
70 |
0.51 |
9.4 |
1.4 |
1.4 |
18.5 |
0.272 |
0.277 |
3.5 |
820 |
100 |
95 |
0.51 |
11.0 |
1.6 |
1.5 |
21.5 |
0.206 |
0.210 |
3.5 |
1110 |
100 |
120 |
0.51 |
12.4 |
1.6 |
1.5 |
23.0 |
0.161 |
0.164 |
3.5 |
1370 |
100 |
150 |
0.51 |
13.8 |
1.8 |
1.6 |
26.0 |
0.129 |
0.132 |
3.5 |
1680 |
100 |
185 |
0.51 |
15.3 |
2.0 |
1.7 |
28.0 |
0.106 |
0.108 |
3.5 |
2070 |
100 |
240 |
0.51 |
17.5 |
2.2 |
1.8 |
32.0 |
0.0801 |
0.0817 |
3.5 |
2710 |
100 |
300 |
0.51 |
19.5 |
2.4 |
1.9 |
35.5 |
0.0641 |
0.0654 |
3.5 |
- |
100 |
Conductor |
Thickness of
insulation
Specified value |
Sheathed
Thickness |
Mean
Overall
Diameter |
Max. Conductor
Resistance 20℃ |
Test
Voltage |
Approx.
Weight |
Packing
Length |
Nominal cross
-sectional
area |
Maximum
Diameter
of wire |
Approx.
Diameter |
Copper |
Tinned |
mm² |
mm |
mm |
mm |
mm |
mm |
Ω/km |
Ω/km |
kV |
kg/km |
m |
1.0 |
0.21 |
1.3 |
0.8 |
1.8 |
10.0 |
19.5 |
20.0 |
3.5 |
120 |
300 |
1.5 |
0.26 |
1.4 |
0.8 |
1.8 |
10.5 |
13.3 |
13.7 |
3.5 |
130 |
300 |
2.5 |
0.26 |
1.8 |
0.8 |
1.8 |
11.5 |
7.98 |
8.21 |
3.5 |
160 |
300 |
4 |
0.31 |
2.3 |
1.0 |
1.8 |
13.5 |
4.95 |
5.09 |
3.5 |
220 |
300 |
6 |
0.31 |
2.8 |
1.0 |
1.8 |
15.5 |
3.30 |
3.39 |
3.5 |
290 |
300 |
10 |
0.41 |
3.6 |
1.0 |
1.8 |
17.5 |
1.91 |
1.95 |
3.5 |
400 |
300 |
16 |
0.41 |
4.5 |
1.0 |
1.8 |
20.0 |
1.21 |
1.24 |
3.5 |
530 |
300 |
25 |
0.41 |
5.6 |
1.2 |
1.8 |
23.5 |
0.780 |
0.795 |
3.5 |
770 |
100 |
35 |
0.41 |
6.7 |
1.2 |
1.8 |
26.5 |
0.554 |
0.565 |
3.5 |
- |
100 |
50 |
0.41 |
8.0 |
1.4 |
1.9 |
30.5 |
0.386 |
0.393 |
3.5 |
- |
100 |
70 |
0.51 |
9.4 |
1.4 |
2.1 |
35.5 |
0.272 |
0.277 |
3.5 |
- |
100 |
95 |
0.51 |
11.0 |
1.6 |
2.2 |
40.5 |
0.206 |
0.210 |
3.5 |
- |
100 |
Conductor |
Thickness of
insulation
Specified value |
Sheathed
Thickness |
Mean
Overall
Diameter |
Max. Conductor
Resistance 20℃ |
Test
Voltage |
Approx.
Weight |
Packing
Length |
Nominal cross
-sectional
area |
Maximum
Diameter
of wire |
Approx.
Diameter |
Copper |
Tinned |
mm² |
mm |
mm |
mm |
mm |
mm |
Ω/km |
Ω/km |
kV |
kg/km |
m |
1.0 |
0.21 |
1.3 |
0.8 |
1.8 |
10.5 |
19.5 |
20.0 |
3.5 |
140 |
300 |
1.5 |
0.26 |
1.4 |
0.8 |
1.8 |
11.0 |
13.3 |
13.7 |
3.5 |
160 |
300 |
2.5 |
0.26 |
1.8 |
0.8 |
1.8 |
12.0 |
7.98 |
8.21 |
3.5 |
200 |
300 |
4 |
0.31 |
2.3 |
1.0 |
1.8 |
14.0 |
4.95 |
5.09 |
3.5 |
280 |
300 |
6 |
0.31 |
2.8 |
1.0 |
1.8 |
16.0 |
3.30 |
3.39 |
3.5 |
370 |
300 |
10 |
0.41 |
3.6 |
1.0 |
1.8 |
19.0 |
1.91 |
1.95 |
3.5 |
520 |
300 |
16 |
0.41 |
4.5 |
1.0 |
1.8 |
21.5 |
1.21 |
1.24 |
3.5 |
700 |
300 |
25 |
0.41 |
5.6 |
1.2 |
1.8 |
25.0 |
0.780 |
0.795 |
3.5 |
- |
100 |
35 |
0.41 |
6.7 |
1.2 |
1.8 |
28.0 |
0.554 |
0.565 |
3.5 |
- |
100 |
50 |
0.41 |
8.0 |
1.4 |
2.0 |
33.0 |
0.386 |
0.393 |
3.5 |
- |
100 |
70 |
0.51 |
9.4 |
1.4 |
2.2 |
38.0 |
0.272 |
0.277 |
3.5 |
- |
100 |
95 |
0.51 |
11.0 |
1.6 |
2.3 |
43.5 |
0.206 |
0.210 |
3.5 |
- |
100 |
0.6/1kV VCT Four Cores (Looking for over 5 Cores, you are recommended to visit the company.) |
Conductor |
Thickness of
insulation
Specified value |
Sheathed
Thickness |
Mean
Overall
Diameter |
Max. Conductor
Resistance 20℃ |
Test
Voltage |
Approx.
Weight |
Packing
Length |
Nominal cross
-sectional
area |
Maximum
Diameter
of wire |
Approx.
Diameter |
Copper |
Tinned |
mm² |
mm |
mm |
mm |
mm |
mm |
Ω/km |
Ω/km |
kV |
kg/km |
m |
1.0 |
0.21 |
1.3 |
0.8 |
1.8 |
11.0 |
19.5 |
20.0 |
3.5 |
170 |
300 |
1.5 |
0.26 |
1.4 |
0.8 |
1.8 |
12.0 |
13.3 |
13.7 |
3.5 |
190 |
300 |
2.5 |
0.26 |
1.8 |
0.8 |
1.8 |
13.0 |
7.98 |
8.21 |
3.5 |
240 |
300 |
4 |
0.31 |
2.3 |
1.0 |
1.8 |
15.0 |
4.95 |
5.09 |
3.5 |
340 |
300 |
6 |
0.31 |
2.8 |
1.0 |
1.8 |
17.5 |
3.30 |
3.39 |
3.5 |
460 |
300 |
10 |
0.41 |
3.6 |
1.0 |
1.8 |
20.5 |
1.91 |
1.95 |
3.5 |
650 |
300 |
16 |
0.41 |
4.5 |
1.0 |
1.8 |
23.5 |
1.21 |
1.24 |
3.5 |
900 |
300 |
25 |
0.41 |
5.6 |
1.2 |
1.8 |
28.0 |
0.780 |
0.795 |
3.5 |
- |
100 |
35 |
0.41 |
6.7 |
1.2 |
1.9 |
31.0 |
0.554 |
0.565 |
3.5 |
- |
100 |
50 |
0.41 |
8.0 |
1.4 |
2.1 |
36.5 |
0.386 |
0.393 |
3.5 |
- |
100 |
70 |
0.51 |
9.4 |
1.4 |
2.3 |
42.0 |
0.272 |
0.277 |
3.5 |
- |
100 |
95 |
0.51 |
11.0 |
1.6 |
2.5 |
48.5 |
0.206 |
0.210 |
3.5 |
- |
100 |
|
|