HOME FITS CABLE INTRANET KOREAN ENGLISH JAPANESE MONGOLIA
> Products > BARE COPPER CONDUCTOR >
Annealed Bare Copper Stranded Wire for Electrical Purposes(WOA, WOAS)


   Annealed Bare Copper Stranded Wire for Electrical Purposes(WOA, WOAS)
Applications Used for electrical conductor
Construction Annealed Copper Wire
Standard KS C 3103 / KS C 3101


Nominal Sectional Area Number & Diameter of Wire Calculated Sectional Area Overall Diameter Standard Weight
Max Conductor Resistance at 20℃ Standard Length
No./mm mm kg/km Ω/km m
0.5 7/0.32 0.56 0.96 5.09 36.0 300
0.75 7/0.37 0.752 1.11 6.84 24.5
1 7/0.40 0.89 1.20 7.90 18.1
1.5 7/0.53 1.54 1.59 13.85 12.1
2.5 7/0.67 2.47 2.01 22.14 7.41
4 7/0.85 3.97 2.55 35.64 4.61
6 7/1.04 5.95 3.12 53.38 3.08
10 7/1.35 10.02 4.05 89.92 1.83
16 7/1.70 15.89 5.10 142.61 1.15
25 7/2.14 25.18 6.42 225.87 0.727
35 7/2.52 34.91 7.56 313.57 0.524
50 19/1.78 47.28 8.90 426.62 0.387
70 19/2.14 68.34 10.70 616.68 0.268
95 19/2.52 94.76 12.60 854.91 0.193
120 37/2.03 119.75 14.21 1084.59 0.153
150 37/2.25 147.11 15.75 1331.92 0.124
185 37/2.52 184.54 17.64 1671.85 0.0991
240 61/2.25 242.54 20.25 2211.04 0.0754
300 61/2.52 304.24 22.68 2775.72 0.0601
400 61/2.85 389.14 25.65 3549.98 0.0470
500 61/3.20 490.59 28.80 4470.04 0.0366